Paper Publications

Particle concentrations and sizes in an air-conditioned office with normal efficiency air filtration of University

Release time:2024-08-09
Hits:
Affiliation of Author(s):
建筑设备科学与工程学院
Journal:
EPPH - iCBBE 2010
Key Words:
中文关键字:质量效率;I/O;粒子浓度;办公室,英文关键字:particle concentration;office; I/O ratio; mass eff
Abstract:
the indoor and outdoor particle number concentrations of different size ranges (0.3-0.5μm, 0.5-1.0μm, 1.0- 3.0μm, 3.0-5.0μm, and ≥10.0μm) were measured in an airconditioned office without tobacco smoking and fresh air. The total mass efficiency of the normal filter installed in the air handing system was measured and calculated to below the 9%, which is much smaller than the efficiency of the filters specified by ASHRAE. Experiments further revealed that the larger particles have the higher filtration efficiency, so the ratios of the concentration of the indoor to outdoor (I/O) decreased with the particles increased. And for the ranges of particle size measured (> 0.3 μm), the indoor particle number concentrations were considerably less than that in outdoor. But for the ratios of I/O, there is a sharp down before the 2.0μm and then a slightly decline.
Note:
樊越胜EI收录
Co-author:
PengfeiSi,AnguiLi,BaoBai,XiangweiZhao
First Author:
fanyuesheng
Indexed by:
Journal paper
Volume:
卷:
Issue:
期:
Page Number:
页:
Translation or Not:
no
Date of Publication:
2010-06-01