王莹莹

邮箱:

所属单位:建筑设备科学与工程学院
发表刊物:Energy and Buildings
关键字:中文关键字:热湿传递;夜间通风量;室内环境;空调负荷,英文关键字:Heat and moisture transfer; Night ventilation rate
摘要:Night ventilation may improve the indoor air temperature and reduce the cooling load. However, the effects of different night ventilation rates on the indoor air relative humidity, wall inner surface temperature, inner surface moisture flux, sensible heat load, latent heat load and total load are rarely studied in terms of the inner surface moisture transfer. The present paper aims to investigate the effect of different night ventilation rates on the above items in a hot-humid climate in China. The results show the following: when the moisture absorption–desorption process at the wall inner surface is not considered, the air-conditioning load of the night ventilation at 15ACH is approximately 5% lower than that at 5ACH. When the moisture absorption–desorption process is considered, the night ventilation rate has a smaller impact on the indoor air temperature and has a larger impact on the indoor air relative humidity during the night. The night ventilation rate negatively correlates with the sensible heat load and positively correlates with the latent heat load due to the increased amount of moisture that is absorbed or desorbed at the interior wall surface. The total air-conditioning load of Case B.1, which featured a 15ACH night ventilation rate, was approximately 8% higher than that of Case A.1, which featured a 5ACH night ventilation rate.
备注:刘艳峰
第一作者:刘加平,王登甲,刘艳峰,王莹莹
论文类型:期刊论文
卷号:卷:80
期号:期:9
页面范围:页:336-374
是否译文:否
发表时间:2014-09-01