访问量:   最后更新时间:--

张莹

硕士生导师
教师姓名:张莹
教师拼音名称:Zhang Ying
所在单位:建筑设备科学与工程学院
学历:博士研究生
性别:女
联系方式:zhangying@xauat.edu.cn
学位:工学博士学位
职称:副教授
在职信息:在职
主要任职:教育部低碳建筑环境国际合作联合实验室 副主任
毕业院校:西安建筑科技大学
所属院系:建筑设备科学与工程学院
其他联系方式

邮箱:

论文成果
Prediction of carbon monoxide concentration and optimization of the smoke exhaust system in a busbar corridor
发布时间:2024-08-09    点击次数:

所属单位:建筑设备科学与工程学院

发表刊物:Building Simulation

关键字:中文关键字:排烟;一氧化碳浓度;火灾动态模拟;廊道火灾,英文关键字:smoke exhaust;carbon monoxide concentration;FDS;co

摘要:Fire in underground structures can result in devastating consequences in terms of both economic damage and loss of life. Hydro-electric plants are typically underground windowless structures. In an underground hydropower station, the busbar corridor connects the busbar layer in the main power plant with the main transformer chamber. This structure forms the channel that is crucial for electrical power transmission. In this paper, a computational method, Fire Dynamics Simulator (FDS), was carried out on a model of a two-story busbar corridor structure based on actual fire test results as a validation case. Twenty-four prediction conditions were taken into account to evaluate the original design of the exhausting system and optimize the busbar corridor modeled smoke control scheme. In those predictions five factors were varied: the heat release rate (HRR), the story height, the air change rate (ACH), the exhaust outlet positions and the airflow inlet positions. Since toxic compounds, especially carbon monoxide, endanger evacuating people in fire scenarios, the carbon monoxide (CO) concentration was reported and used throughout this study as an indicator of the safety of occupants in the corridor. Of the five varied factors it was found that the story height and the airflow inlets with natural ventilation influenced the smoke suppression and control. For the story height of 6.0 m, the filling time is 52 s more than the story height of 4.5 m. The CO concentration of opening set upstairs only is twice as much of the design condition. Opening set downstairs only can exhaust smoke faster for occupied area.

备注:李安桂

合写作者:李安桂等

第一作者:张莹

论文类型:期刊论文

卷号:卷:7

期号:期:6

页面范围:页:639-648

是否译文:

发表时间:2014-12-01